Correction! In the book a transformer ratio of 14,000/480-V is given. This should be 14,400/480-V which is also used in the following calculations.
A 14,400/480-V three-phase Y-$\Delta$-connected transformer bank consists of three identical 100-kVA 8314/480-V transformers. It is supplied with power directly from a large constant-voltage bus. In the short-circuit test, the recorded values on the high-voltage side for one of these transformers are:
$$V_{SC} = 510\,V \qquad I_{SC} = 12.6\,A \qquad P_{SC} = 3000\,W$$
In [2]:
Sbase = 100e3 # [VA]
Vp_ll = 14400 # [V] primary line-to-line volage of transformer bank
Vs_ll = 480 # [V] secondary line-to-line volage of transformer bank
Vp_ph = 8314 # [V] primary phase voltage of single transformer
Vs_ph = 480 # [V] secondary phase voltage of single transformer
If this bank delivers a rated load at 0.8 PF lagging and rated voltage
Assume that the primary phase voltage of this transformer is a constant 8314 V
From the short-circuit information, it is possible to determine the per-phase impedance of the transformer bank referred to the high-voltage (primary) side. Note that the short-circuit information is given for one transformer of the three in the bank. The voltage across this transformer is:
In [3]:
Vphi_SC = 510 # [V]
the short-circuit phase current is:
In [4]:
Iphi_SC = 12.6 # [A]
and the power per phase is:
In [5]:
Pphi_SC = 3000.0 # [W]
Thus the per-phase impedance is: $$|Z_\text{EQ}| = |R_\text{EQ} + jX_\text{EQ}| = \frac{V_{\phi,SC}}{I_{\phi,SC}}$$
In [6]:
Zeq = Vphi_SC / Iphi_SC
print('|Zeq| = {:.2f} Ω'.format(Zeq))
In [7]:
theta = arccos(Pphi_SC / (Vphi_SC*Iphi_SC))
print('theta = {:.1f}°'.format(theta/pi *180))
In [8]:
ZEQ = Zeq * (cos(theta) + sin(theta)*1j)
print('ZEQ = {:.2f} Ω'.format(ZEQ))
In [9]:
Req = ZEQ.real
Xeq = ZEQ.imag
print('''
Req = {:.2f} Ω
Xeq = j{:.2f} Ω
'''.format(Req, Xeq))
If this Y-$\Delta$ transformer bank delivers rated kVA (300 kVA) at 0.8 power factor lagging while the secondary voltage is at rated value, then each transformer delivers 100 kVA at a voltage of 480 V and 0.8 PF lagging. Referred to the primary side of one of the transformers, the load on each transformer is equivalent to 100 kVA at 8314 V and 0.8 PF lagging. The equivalent current flowing in the secondary of one transformer referred to the primary side is:
In [10]:
PF = 0.8
V_PHI_s = Vp_ph # secondary phase voltage as referred by the primary side
I_phi_s = Sbase / abs(V_PHI_s) # amplitude of current
I_PHI_s_angle = -arccos(PF) # angle
I_PHI_s = I_phi_s * (cos(I_PHI_s_angle) + sin(I_PHI_s_angle)*1j) # complex vector
print('I_PHI_s = {:.2f} A ∠{:.2f}°'.format(
abs(I_PHI_s), I_PHI_s_angle/pi * 180))
The voltage on the primary side of a single transformer is thus: $$\vec{V}_{\phi,P} = \vec{V}'_{\phi,S} + \vec{I}'_{\phi,S}Z_{EQ,P}$$
In [11]:
V_PHI_p = V_PHI_s + I_PHI_s*ZEQ
V_PHI_p_angle = arctan(V_PHI_p.imag/V_PHI_p.real)
print('V_PHI_p = {:.0f} V ∠{:.2f}°'.format(
abs(V_PHI_p), V_PHI_p_angle/pi * 180))
The line-to-line voltage on the primary of the transformer is:
$$V_{LL,P} = \sqrt{3}V_{\phi,P}$$
In [12]:
Vll_p = sqrt(3) * abs(V_PHI_p)
print('''
Vll_p = {:.2f} kV
================
'''.format(Vll_p/1000))
In [13]:
V_PHI_s
Out[13]:
In [14]:
VR = (abs(V_PHI_p) - abs(V_PHI_s)) / abs(V_PHI_s) * 100
print('''
VR = {:.2f} %
===========
'''.format(VR))
In [15]:
Sbase_3 = 300e3 # [VA]
Vll_base = Vp_ll
Vll_base
Out[15]:
In [16]:
Il_base = Sbase_3 / (sqrt(3)*Vll_base)
print('Il_base = {:.2f} A'.format(Il_base))
The transformer bank is connected in "Y" which means for the base phase current that:
$$I_{\phi_\text{base}} = \frac{I_{L_\text{base}}}{\sqrt{3}}$$
In [17]:
Iphi_base = Il_base / sqrt(3)
print('Iphi_base = {:.2f} A'.format(Iphi_base))
This sort of repetitive operation is best performed with Python. Note that in this case, the problem is specifying a fixed primary phase voltage of 8314 V, and asking what the secondary voltage will be as a function of load. Therefore, we must subtract the voltage drop inside the transformer at each load, and convert the resulting voltage from the primary side to the secondary (low voltage) side.
Define values for this transformer:
In [18]:
VL = Vp_ll # [V] primary line voltage
VP = VL / sqrt(3) # [V] primary phase voltage
amps = linspace(0, Il_base, 100) # [A] phase current values
# Req is Equivalent R, which is already defined
# Xeq is Equivalent X, which is already defined
Calculate the current values for the three power factors.
In [19]:
re = 0.85
im = sin(arccos(re))
I = amps * array ([[re - im*1j], # lagging
[1.0], # unity
[re + im*1j]]) # leading
Calculate secondary phase voltage referred to the primary side for each current and power factor.
In [20]:
aVSP = VP - (Req*I + 1j*Xeq*I)
Refer the secondary phase voltages back to the secondary side using the turns ratio. Because this is a delta-connected secondary, this is also the line voltage.
In [21]:
a = Vp_ph/Vs_ph # turns ratio
VSP = aVSP / a
Plot the secondary voltage versus load:
In [22]:
title('Secondary voltage vs load current')
xlabel('Load current [A]')
ylabel('Secondary voltage [V]')
plot(amps, abs(VSP[0,]), 'b-',
amps, abs(VSP[1,]), 'k--',
amps, abs(VSP[2,]), 'r-.',
linewidth = 2)
legend(('0.8 PF lagging', '1.0 PF', '0.8 PF leading'), loc=3);
grid()
Calculate the voltage regulation:
In [23]:
VR = (VP - abs(aVSP)) / abs(aVSP) * 100
Plot the voltage regulation versus load:
In [24]:
title('Voltage Regulation vs load current')
xlabel('Load current [A]')
ylabel('Voltage Regulation [%]')
plot(amps, abs(VR[0,]), 'b-',
amps, abs(VR[1,]), 'k--',
amps, abs(VR[2,]), 'r-.',
linewidth = 2)
legend(('0.8 PF lagging', '1.0 PF', '0.8 PF leading'), loc=0);
axis([0,14,-1,6])
grid()
In [25]:
Vlp = Vp_ll
Vphip_base = Vlp / sqrt(3)
print('Vphip_base = {:.3f} kV'.format(Vphip_base/1000))
The base impedance on the primary side is given by: $$Z_{\text{base}_S} = \frac{(V_{\phi_{\text{base}_S}})^2}{S_{\phi_\text{base}}}$$
In [26]:
Zbase_s = Vphip_base ** 2 / Sbase_3
print('Zbase_s = {:.0f} Ω'.format(Zbase_s))
The per-unit impedance is:
In [27]:
Req_pu = Req / Zbase_s
Xeq_pu = Xeq / Zbase_s
print('''
Req_pu = {:.3f} pu
Xeq_pu = {:.3f} pu
'''.format(Req_pu, Xeq_pu))
The excitation branch information was not given for the transformer.
So the per-unit, per-phase equivalent circuit of the transformer bank is shown below: